← All CVEs

CVE-2018-19616

high · 8.1

An issue was discovered in Rockwell Automation Allen-Bradley PowerMonitor 1000. An unauthenticated user can add/edit/remove administrators because access control is implemented on the client side via a disabled attribute for a BUTTON element.

8.1
CVSS
30.3%
EPSS (exploit prob.)
98th
EPSS percentile
2018-12-26
Published

CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H

Weaknesses

CWE-287

Affected products

VendorProductAffected versions
rockwellautomationpowermonitor_1000_firmware1408-em3a-ent_b
rockwellautomationpowermonitor_1000all versions

Check a specific version with /api/v1/cve/match.

References

Query this programmatically:

curl https://evil-db.io/api/v1/cve/CVE-2018-19616